MID Support ADL400 Three-Phase Din Rail Energy Meter
● Rated Current: 1 (6) A, 10 (80) A
● Rated Voltage: AC220V/380V, AC230V/400V
● RS485(MODBUS-RTU) Communication
● 12 digits LCD Display; 35mm DIN Rail Installation
● 2~31st Harmonic Measurement
● kWh Class 0.5S
- Overview
- Parameter
- Certificates
- Customer Questions & Answers
- Contact us
ADL400 din rail energy meter adopts DIN35mm din rail installation with LCD display,it can measure electric parameters and has energy pulse output, RS485 communication,which has the advantages of small size, high precision, good reliability and convenient installation.
① Voltage Enter-wire
② Brand
③ Panel
④ Up Button
⑤ Down Button
⑥ Auxiliary function
⑦ Pulse Output
⑧ Model
⑨ Set Button
⑩ CT Enter-wire
Functions
Display
Wiring
project | performance parameter | ||
Specification | 3 phase 3 wires, 3 phase 4 wires | ||
Measurement | Voltage | Reference voltage | 3×100V、 3×380V、3×57.7/100V、 3×220/380V |
Consumption | <10VA(Single phase) | ||
Impedance | >2MΩ | ||
Accuracy class | Error±0.2% | ||
Current | Input current | 3×1(6)A, 3×10(80)A | |
Consumption | <1VA Single phase rated current | ||
Accuracy class | Error±0.2% | ||
Power | Active, reactive, apparent power, error±0.5℅ | ||
Frequency | 45~65Hz,Error±0.2% | ||
Metering | Energy | Active energy(Accuracy class: 0.5) reactive energy(Accuracy class 2) | |
Clock | ≤0.5s/d | ||
Digit signal | Energy pulse output | 1 active photocoupler output | |
pulse | Width of pulse | 80±20ms | |
Pulse constant | 400imp/kWh,10000imp/kWh(Correspond with the basic current) | ||
communication | Interface and communication protocol | RS485口:Modbus RTURS485:Modbus RTU | |
Range of communication address | Modbus RTU:1~ 247; | ||
Baud rate | 1200bps~19200bps | ||
environment | working temperature | -25℃~+55℃ | |
Relative humidity | ≤95℅(No condensation) |
-
Manual
Customer Questions & Answers
-
Answer:
Switch the meter display to the power (active power P, power factor λ) interface, and check whether the power display is negative or not. And whether the power factor is between 0.9-0.95, and then check whether the incoming and outgoing wires of the current signal wire are connected reversely (that is, the current The incoming wire must be the same as the incoming wire end of the instrument) and consistent with the wiring diagram on the instrument.
marry August 31, 2022 -
Answer:
1. The voltage value between the communication output A and B of the measuring instrument should be between +(4.4-4.5)V; 2. Check whether the communication wiring method is correctly wired in accordance with the wiring diagram requirements (that is, the communication terminal A/B of the corresponding to communication serial port A/B);
marry August 31, 2022