ACR10R-D16TE Solar Inverter Energy Meter
● Single phase three wire
● Rated voltage: AC 120V/208V,240V(88%~110%)
● Rated voltage: AC 100V or 400V
● Rated current: AC 80A
● RS485(MODBUS-RTU)
● Certificate: CE
- Overview
- Parameter
- Certificates
- Customer Questions & Answers
- Contact us
Application
Solar PV Power Distribution Monitoring Solution
Anti-reflux Function
1.What is anti-reflux?
In the power system, the distribution transformer generally sends power to each load in the grid, which is called forward current.
After installing the photovoltaic power station
When the power of the photovoltaic system is greater than the power of the local load, the power that cannot be absorbed will be sent to the grid. Since the current direction is opposite to the conventional one, it is called "reverse flow".
2.Acrel Photovoltaic Backflow Prevention Solution
Products
Acrel ACR10R-D16TE 1 phase energy meter is a guide rail multifunctional electrical instrument with an external split-core current transformer, which is suitable for applications such as power monitoring of distributed photovoltaic power cabinets, grid-connected cabinets, and energy demand management.
It has the characteristics of no need to disassemble the busbar, convenient wiring, and safe construction, which saves transformation costs for users and improves efficiency. It integrates the measurement of all electrical parameters (including single-phase current, voltage, active power, reactive power, apparent power, frequency, power factor) and comprehensive energy monitoring and assessment management.
Voltage Value:AC 57.7V/100V(100V)、220V/380V(400V) Wiring:Three phase Three wire (3P3W),Three phase Four wire(3P4W) Accuracy:Reactive energy 1 class,others 0.5 classs 1 pc Current Sensor:80A,120A,200A,300A Communicatio:RS485 Interface、MODBUS-RTU Function:Total Harmonic, Sub-harmonic(2-31th) | |
① Brand / Model ② Panel ③ Current Transformer ④ Button ⑤ Indictor Lights |
Dimension
Function
Frequency:45~65Hz |
Power consumption:≤10VAp> |
Power supply output:AC85~265V or DC100~350V |
Input consumption:Less than 0.2VA |
Dimension(L*W*H):85*74*54mm |
Installation:DIN 35mm |
Wiring
Technical parameters | Indicators | ||
Input | Grid | Single-phase | |
Frequency | 45~65Hz | ||
Voltage | Rated voltage: AC 100V, 400V | ||
Overload: 1.2 times the rated voltage(continuous); 2 times the rated voltage lasting for 1 second | |||
Power consumption: less then 0.2VA | |||
Current | Rated current: 10A,20A,40A,80A,120A,200A etc. (for details see product specifications) | ||
Overload: 1.2 times the rated current(continuous);10 times the rated current lasting for 1 second | |||
Power consumption: less then 0.2VA | |||
Output | Communication | RS485 interface, Modbus-RTU | |
Display | LCD | ||
Measurement precision | Voltage: 0.2 level, current, power Active energy: 0.5 level,0.01Hz frequency, Reactive energy: 1 level | ||
Power supply | AC85~265V or DC100~350V; power consumption ≤10VA | ||
Safety | Power frequency withstand voltage | AC2kV 1 min between power supply // current input//voltage input and communicationAC2kV 1 min between each pair of combinations among power supply, urrent input and voltage input. | |
Insulating resistor | Input,output terminal to housing >100MΩ | ||
Environment | Working temperature: -10℃~+55℃;storage temperature: -20℃~+70℃Relative humidity:5%~95%,non-condensing; altitude:≤2500m |
Customer Questions & Answers
-
Answer:
Yes,our ACR10R-D16TE this product includes a meter and a transformer. The system voltage of this single-phase meter is AC220V, the maximum current connection is 120A(via CT), the accuracy is 0.5, and Modbus-RTU RS485 communication.
Liana Song October 13, 2022 -
Answer:
You can contact us and tell us more details, we can tell you if our ACR10R-D10TE is suitable for you based on your information.
Liana Song October 13, 2022