Acrel ADW300 3 Phase IoT Wireless Smart Meter
● Measurement: 3 Phase voltage, current, power, power factor, etc.
● Communication: RS485, LoRa, 4G, NB or 2G
● Max demand
● Accuracy: Class 1
- Overview
- Parameter
- Certificates
- Customer Questions & Answers
- Contact us
ADW300 wireless meter is mainly used to measure three-phase active power in low-voltage network. It has the functions of RS485 communication and 470MHZ wireless communication. It is convenient for users to monitor, collect and manage electricity. It can be flexibly installed in the distribution box to realize the measurement, statistics and analysis of individual electric energy in different regions and loads.
① DO / DI
② Brand
③ Model Number
④ Antenna Terminal
⑤ Pulse Output Light
⑥ Infrared Status
⑦ Auxiliary Power Supply
⑧ Temperature / Leakage Current
Function
Active power: Class 0.5S
Reactive power: Class 2
Pulse Output
Constant: 6400imp/kWh;
Consumption
<10VA(Single phase)
Dimension (L*W*H)
Panel size (L×W):82*87.8*71.5 mm
Wireless
Transmission on 470MHz and maximum distance
in open space is 1km; 2G; NB
Frequency: Range: 50~60Hz
Starting current: 2‰ln
Wiring
3 Phase 3 Wire
3 Phase 4 Wire
3 Phase 4 Wire with External CT
Network
Package
MINIMUM PACKAGE | ||
MINIMUM PACKAGE | Package Dimension(1 PC) 170*150*130mm | |
WHOLE BOX PACKAGE | Package Dimension(36 PCS) 540*530*490mm |
MINIMUM PACKAGE | ||
MINIMUM PACKAGE | Package Weight(1 PC) 0.233Kg | |
WHOLE BOX PACKAGE | Package Weight(36 PCS) 10kG |
ATTENTION !
The above packing and weight data are only refer to model ADW300.
For other models or optional functions, please contact the salesman for details, thank you for your cooperation!
Voltage input | Rated voltage | 3×57.7/100V,3×220/380V,3×380/660V,3×100V, 3×380V,3×660V |
Reference frequency | 50Hz | |
Power waste | each phase<0.5VA | |
Current input | Input current | 3×1(6)A ;3×1(6)A(ADW300W), 3×20(100)A(ADW300W)-HJ:(3×1.5(6)A(D10)、3×20(100)A(D16)、3×80(400)A(D24)、3×120(600)A(D36)) |
Start current | 1‰Ib(class 0.5S),4‰Ib(class 1 ) | |
Power waste | each phase<1VA | |
Auxiliary power supply | Supply voltage | AC 85~265V |
Power waste | <2W | |
Measurement performance | Standard | GB/T17215.322-2008,GB/T17215.321-2008 |
Active energy accuracy | Class 0.5S(ADW300),class 1(ADW300W) | |
Temperature Accuracy | ±2℃ | |
pulse | pulse width | 80±20ms |
Impulse constant | 6400imp/kWh , 400imp/kWh-HJ(6400imp/kWh(D10) 、400imp/kWh(D16)、100imp/kWh(D24)、60imp/kWh(D36)) | |
Communication | wireless | Transmission on 470MHz and maximum distance in open space is 1km;2G;NB;4G |
Infrared communication | The constant baud rate is 1200 | |
Interface | RS485(A、B) | |
Connection mode | Shielded twisted pair conductors | |
Protocol | MODBUS-RTU、DL/T 645-07 |
Customer Questions & Answers
-
Answer:
3*100V、3*57.7/100V used for high voltage , with voltage transformer . 3*100V stands for 3P3W,3*57.7V/100Vstands for 3P4W;3*380V、3*220V/380V、 3x660V、3x380/660V used for low voltage , with voltage directly input .3*380V.3x660V stands for 3P3W,3"220V/380V、3x380/660V stands for 3P4W
Liana March 10, 2023 -
Question:
What is the difference between ordinary secondary access and W ( type external transformer )?
Answer:General secondary access to the built - in transformer . The transformer is selected according to the actual current on site . Model W comes with external transformer ( can not be disassembled , otherwise it will burn the meter ). The transformer has been installed on site for easy wiring and free of disassembly .
Liana March 10, 2023 -
Answer:
Please first confirm whether the RS485 wiring is loose , AB reverse connection and other problems , and then click the key to check the table of general parameters Numbers , such as address , baud rate , check bits , etc ., are set correctly .
Liana March 10, 2023