All Categories
EN

Home > Products > Energy Meter > IOT Wireless Energy Meter

ADW300 IoT Wireless Energy Meter


● Type: Three Phase Energy Meter


● Measurement:U、I、 P、Q、S、PF、F、THDv、Harmonic on 2nd-31st,etc


● Wireless Communication:  4G,WIFI,LoRawan(US915,EU868,EU923),NB-IoT


● Protocol:MQTT,Modbus-Rtu,Modbus-TCP


● Accuracy:0.5S Class


● Extra function:Max 4 loops temperature measurement


● Extra function:Work with Rogowski coil

Email: [email protected]

Mobile: +86 134 8217 7205

Whatsapp/Wechat: +86 134 8217 7205

  • Overview
  • Parameter
  • Certificates
  • Customer Questions & Answers
  • Contact us

ADW300 IoT wireless power meter is mainly used to measure three-phase active power in low-voltage network. It has the functions of RS485 communication and 470MHZ wireless communication. It is convenient for users to monitor, collect and manage electricity. It can be flexibly installed in the distribution box to realize the measurement, statistics and analysis of individual electric energy in different regions and loads.

Voltage inputRated voltage3×57.7/100V,3×220/380V,3×380/660V,3×100V, 3×380V,3×660V
Reference frequency50Hz
Power wasteeach phase<0.5VA
Current inputInput current1A or 5A or 200mV
Start current1‰Ib(class 0.5S),4‰Ib(class 1 )
Power wasteeach phase<1VA
Auxiliary power supplySupply voltageAC 85~265V
Power waste<2W
Measurement performanceStandardGB/T17215.322-2008,GB/T17215.321-2008
Active energy accuracyClass 0.5S(ADW300),class 1(ADW300W)
Temperature Accuracy±2℃
pulsepulse width80±20ms
Impulse constant6400imp/kWh , 400imp/kWh-HJ(6400imp/kWh(D10) 、400imp/kWh(D16)、100imp/kWh(D24)、60imp/kWh(D36))
Communicationwireless communicationLoRawan;WIFI;NB-IoT;4G
Infrared The constant baud rate is 1200
InterfaceRS485(A、B)
Connection modeShielded twisted pair conductors
ProtocolMODBUS-RTU、DL/T 645-07、MQTT、Modbus-TCP



ADW300 IoT Wireless Energy Meter


undefined

3x1(6) A ;3x1(6) A (ADW300),3x20(100) A (ADW300W)


● U 、 I 、 P 、 Q 、 S 、 PF 、 F 、 KWH 、 KVARH
●2DO 4DI
●4 WAY TEMPERATURE MEASURE ,1 WAY RESIDUAL CURRENT
●35 MM DIN RAIL


Wiring3P3W/3P4W
Accuracy0.5S calss (ADW300)   1class(ADW300W)
Voltage3x57.7/100V,3x220/380V,660V
CommunicationRS485, LoRawan, WIFI , NB-IoT ,4G
Size72x87.8x71.5( MM )


Function


4-2

Accuracy
Active power: Class 0.5S
Reactive power: Class 2

Pulse Output
Constant: 6400imp/kWh;

Consumption
<10VA(Single phase)




4-3

Dimension (L*W*H)
Panel size (L×W):82*87.8*71.5 mm

Wireless
Transmission on 470MHz and maximum distance
in open space is 1km; 2G; NB

Frequency: Range: 50~60Hz

Starting current: 2‰ln





Special Aplication

8f620ae06a93b7aecdee82f2ad5e197



Wiring

4-4

4-5

3 Phase 3 Wire

4-6

3 Phase 4 Wire

4-7

3 Phase 4 Wire with External CT


Network








4-11


Package


MINIMUM PACKAGE4-124-13
MINIMUM PACKAGEPackage Dimension(1 PC)
170*150*130mm
WHOLE BOX PACKAGEPackage Dimension(36 PCS)
540*530*490mm


MINIMUM PACKAGE4-144-15
MINIMUM PACKAGEPackage Weight(1 PC)
0.233Kg
WHOLE BOX PACKAGEPackage Weight(36 PCS)
10kG


ATTENTION !
The above packing and weight data are only refer to model ADW300.
For other models or optional functions, please contact the salesman for details, thank you for your cooperation!


Voltage inputRated voltage3×57.7/100V,3×220/380V,3×380/660V,3×100V, 3×380V,3×660V
Reference frequency50Hz
Power wasteeach phase<0.5VA
Current inputInput current3×1(6)A ;3×1(6)A(ADW300W), 3×20(100)A(ADW300W)-HJ:(3×1.5(6)A(D10)、3×20(100)A(D16)、3×80(400)A(D24)、3×120(600)A(D36))
Start current1‰Ib(class 0.5S),4‰Ib(class 1 )
Power wasteeach phase<1VA
Auxiliary power supplySupply voltageAC 85~265V
Power waste<2W
Measurement performanceStandardGB/T17215.322-2008,GB/T17215.321-2008
Active energy accuracyClass 0.5S(ADW300),class 1(ADW300W)
Temperature Accuracy±2℃
pulsepulse width80±20ms
Impulse constant6400imp/kWh , 400imp/kWh-HJ(6400imp/kWh(D10) 、400imp/kWh(D16)、100imp/kWh(D24)、60imp/kWh(D36))
CommunicationwirelessTransmission on 470MHz and maximum distance in open space is 1km;2G;NB;4G
Infrared communicationThe constant baud rate is 1200
InterfaceRS485(A、B)
Connection modeShielded twisted pair conductors
ProtocolMODBUS-RTU、DL/T 645-07



Customer Questions & Answers
    Did not match any questions!
Your Name
E-mail *
Phone/Whatsapp
Country
Your identity (dealer or individual)
Your Inquiry *
Clicky