All Categories
EN

Home > Products > Energy Meter > IOT Wireless Energy Meter

ADW300 IoT Wireless Energy Meter


● Measurement: 3 Phase voltage, current, power, power factor, etc.

● Wireless Communication:  4G,WIFI, 2G,RS485
● Max demand

● Accuracy: Class 1

Email: [email protected]

Mobile: +86 134 8217 7205

Whatsapp/Wechat: +86 134 8217 7205

  • Overview
  • Parameter
  • Certificates
  • Customer Questions & Answers
  • Contact us

ADW300 IoT wireless power meter is mainly used to measure three-phase active power in low-voltage network. It has the functions of RS485 communication and 470MHZ wireless communication. It is convenient for users to monitor, collect and manage electricity. It can be flexibly installed in the distribution box to realize the measurement, statistics and analysis of individual electric energy in different regions and loads.

Voltage input Rated voltage 3×57.7/100V,3×220/380V,3×380/660V,3×100V, 3×380V,3×660V
Reference frequency 50Hz
Power waste each phase<0.5VA
Current input Input current 3×1(6)A ;3×1(6)A(ADW300W), 3×20(100)A(ADW300W)-HJ:(3×1.5(6)A(D10)、3×20(100)A(D16)、3×80(400)A(D24)、3×120(600)A(D36))
Start current 1‰Ib(class 0.5S),4‰Ib(class 1 )
Power waste each phase<1VA
Auxiliary power supply Supply voltage AC 85~265V
Power waste <2W
Measurement performance Standard GB/T17215.322-2008,GB/T17215.321-2008
Active energy accuracy Class 0.5S(ADW300),class 1(ADW300W)
Temperature Accuracy ±2℃
pulse pulse width 80±20ms
Impulse constant 6400imp/kWh , 400imp/kWh-HJ(6400imp/kWh(D10) 、400imp/kWh(D16)、100imp/kWh(D24)、60imp/kWh(D36))
Communication wireless Transmission on 470MHz and maximum distance in open space is 1km;2G;NB;4G
Infrared communication The constant baud rate is 1200
Interface RS485(A、B)
Connection mode Shielded twisted pair conductors
Protocol MODBUS-RTU、DL/T 645-07



ADW300 IoT Wireless Energy Meter


undefined

3x1(6) A ;3x1(6) A (ADW300),3x20(100) A (ADW300W)


● U 、 I 、 P 、 Q 、 S 、 PF 、 F 、 KWH 、 KVARH
●2 WAY DO ,4 WAY DI
●4 WAY TEMPERATURE MEASURE ,1 WAY RESIDUAL CURRENT
●35 MM DIN RAIL


Wiring 3P3W/3P4W
Accuracy 0.5S calss (ADW300)   1class(ADW300W)
Voltage 3x57.7/100V,3x220/380V,660V
Communication RS485, LORA (47OMHZ), WIFI , NB ,4G

protocol MODBUS - RTU 、 DL / T 64-07

Size 72x87.8x71.5( MM )


Function



Accuracy
Active power: Class 0.5S
Reactive power: Class 2

Pulse Output
Constant: 6400imp/kWh;

Consumption
<10VA(Single phase)

4-2



4-3

Dimension (L*W*H)
Panel size (L×W):82*87.8*71.5 mm

Wireless
Transmission on 470MHz and maximum distance
in open space is 1km; 2G; NB

Frequency: Range: 50~60Hz

Starting current: 2‰ln

Wiring

4-4

4-5

3 Phase 3 Wire

4-6

3 Phase 4 Wire

4-7

3 Phase 4 Wire with External CT


Network


4-8


4-9


4-10


4-11


Package


MINIMUM PACKAGE 4-12 4-13
MINIMUM PACKAGE Package Dimension(1 PC)
170*150*130mm
WHOLE BOX PACKAGE Package Dimension(36 PCS)
540*530*490mm


MINIMUM PACKAGE 4-14 4-15
MINIMUM PACKAGE Package Weight(1 PC)
0.233Kg
WHOLE BOX PACKAGE Package Weight(36 PCS)
10kG


ATTENTION !
The above packing and weight data are only refer to model ADW300.
For other models or optional functions, please contact the salesman for details, thank you for your cooperation!


Voltage inputRated voltage3×57.7/100V,3×220/380V,3×380/660V,3×100V, 3×380V,3×660V
Reference frequency50Hz
Power wasteeach phase<0.5VA
Current inputInput current3×1(6)A ;3×1(6)A(ADW300W), 3×20(100)A(ADW300W)-HJ:(3×1.5(6)A(D10)、3×20(100)A(D16)、3×80(400)A(D24)、3×120(600)A(D36))
Start current1‰Ib(class 0.5S),4‰Ib(class 1 )
Power wasteeach phase<1VA
Auxiliary power supplySupply voltageAC 85~265V
Power waste<2W
Measurement performanceStandardGB/T17215.322-2008,GB/T17215.321-2008
Active energy accuracyClass 0.5S(ADW300),class 1(ADW300W)
Temperature Accuracy±2℃
pulsepulse width80±20ms
Impulse constant6400imp/kWh , 400imp/kWh-HJ(6400imp/kWh(D10) 、400imp/kWh(D16)、100imp/kWh(D24)、60imp/kWh(D36))
CommunicationwirelessTransmission on 470MHz and maximum distance in open space is 1km;2G;NB;4G
Infrared communicationThe constant baud rate is 1200
InterfaceRS485(A、B)
Connection modeShielded twisted pair conductors
ProtocolMODBUS-RTU、DL/T 645-07