AMC16Z-FAK48 Multi Channel Data Center Ac Smart Meter
● Designed specifically for the power supply management of server in the data center
● A+B independent 24 circuits(48 in total)
● U, I, P, Q, S, PF, kWh, kvarh
● 2nd-31st Harmonic
● kWh Class 0.5
● DIN 35 mm
- Overview
- Parameter
- Certificates
- Customer Questions & Answers
- Contact us
AMC16Z series multi channel din rail ac power meter is independently designed to meet the needs of the increasingly high precision power distribution management requirements of the data center. It is suitable for carious all-round inrelligent monitoring of terminal distribution equipment.
● 24 channels of each circuit of A+B
● independent 2 circuits the outgoing current,
● active power, active power, reactive power
● 2-31st harmonic, 48DI
● 1 RS485 communication
Installation:
DIN rail 35mm
Dimension(L*W*H):
180*94.3*75mm
Network
Package
MINIMUM PACKAGE | ![]() | ![]() |
MINIMUM PACKAGE | Package dimensions(1 PC) 220*170*90mm | |
WHOLE BOX PACKAGE | Package dimensions(24 PC) 615*480*395mm |
MINIMUM PACKAGE | ![]() | ![]() |
MINIMUM PACKAGE | Pakage Weight(1 PC) 0.28Kg | |
WHOLE BOX PACKAGE | Pakage Weight(24 PC) 6.72Kg |
ATTENTION !
The above packing and weight data are only refer to model AMC16Z-FAK48.
For other models or optional functions, please contact the salesman for details, thank you for your cooperation!
Technical parameters | AMC16Z-FAK24 | AMC16Z-FAK48 | |
Measurement parameters | Voltage, current, frequency, active power, reactive power, power factor, active power, reactive power, switching state | ||
2-31 times harmonics | |||
Bus Voltage | Rated | 220VAC | |
Measurement | ±20% | ||
Overload | Instantaneous voltage 2 times/second | ||
Current outgoing line loop | Rated | 50mA | |
Range | 0.125~60mA | ||
Overload | Duration 1.2 times, instantaneous 10 times/second | ||
Input frequency | 45~60Hz | ||
Measurement accuracy | Outgoing line | Voltage/current/active power/active energy level 0.5, reactive power/reactive energy level 1 | |
Auxiliary power supply | Power supply by AMC16Z-ZA | ||
Environment | Temperature | Working:-15℃~55℃ Storage:-25℃~70℃ | |
Humidity | Relative humidity | ||
Altitude | ≤2500m | ||
Communication | RS485/Modbus-RTU | ||
Installation method | DIN35mm Guide rail or bottom plate mounting | ||
IP grade | IP20 | ||
Class of pollution | 2 | ||
Safety | Insulation | All terminals and the insulation resistance between the conductive pieces not below 100 m Ω | |
Withstand voltage | A-channel voltage and current signal // B-channel voltage and current signal // other ports meet AC2kV 1min between pairs, leakage current should be less than 2mA, no breakdown or flashover phenomenon. | ||
Electromagne tic compatibility | Anti static interference | Level 4 | |
Resistance to radiation of Radio frequency electromagneti | Level 3 |