Acrel AMC16-DETT DC 6 Circuits Power Meter
Application:Base stations
6 circuits DC energy
Alarm, data storage and processing, data interaction
- Overview
- Customer Questions & Answers
- Contact us
Overview
Base station dedicated DC energy meter AMC16-DETT is specially designed for base stations where have sharing requirements, and switch power supply is without the function of sub-user metering. The meter could measure 6 circuits DC energy, and supply working current to the matched hall sensors. Meanwhile, it can realize zero drift calibration by upper computer software.
have the functions of telemetering,teleindication,teleadjusting, metering at real time, energy quality abnormal alarm, data storage and processing, data interaction. This meter can measure DC power consumption of three operators, providing detail datas for base station.
MODEL
NAME | MODEL | INSTALLATION |
Base station DC energy meter | AMC16-DETT | 35mm din rail |
SPECIFICATIONS
Technical parameter | Index | |
input | DC rated voltage | 1 channel: -48VDC |
DC current | 6 channels hall sensors: total 200A/5V, China Telecom, China Mobile, China Unicom and the 1st channel reserve 50A/5V, 2nd channel reserve 100A/5V. | |
Commercial power monitoring | 1 channel: 0-5VDC | |
Overload capacity | Voltage:1.2times continued,2 times continued 1s; Current: 1.2 times continued,10 times continued 1s. | |
Accuracy (superposition hall sensors) | 1%In≤I≤10%In error±2.5%; I>10%In error±2% | |
Measurement resolution | Voltage output accuracy 0.01V; current output accuracy 0.01A; power output accuracy 0.01kw; energy output accuracy 0.01kwh | |
functions | Basic function | Monitor device system time, total voltage, output total current, power, energy, each channel voltage, current, power, energy; LED indicator display;485 communication |
Metering function | Start current: under rated voltage, when the load current value of the meter doesn’t exceed 1% of the max. current, the meter starts. Shunt running current: when there is no current in the current circuit of the meter, and 85%-125%of the rated voltage is applied on the voltage circuit, the calculator shall not have more than one digital change | |
Alarm function | DC voltage output low alarm,DC voltage output high alarm,one power down alarm, module voltage loss alarm, metering branch error alarm, internal program error alarm, clock error alarm, memory failure alarm, AC input power failure alarm | |
Timing function | support broadcast timing, could remote timing to the meter through RS485 communication. | |
Communication | Single channel RS485, baudrate 9600bps, can be set to 1200BPS, 2400bps, 4800bps. Communication protocol: standard or custmized | |
Hall sensor power supply | Power supply output:+12V/100Ma, -12V/50mA | |
Clock accuracy | ≤0.5S/d(23℃), ≤1S/d(-20℃-60℃), | |
Auxiliary power supply | Voltage range | -40V~-60VDC |
Power consumption | Whole device≤2W( no hall power supply output) |
DIMENSION
INSTALLATION AND WIRINGS
Note: arrow direction should be the same with current direction marked on the sensor .
1. input voltage should not be higher than 120% of product’s rated input voltage, must install
1A fuse at the voltage input terminal.
2. Current input should use external diverter or hall sensor.
3. To ensure the accuracy,the DC meter should used together with Acrel hall sensors, the wiring length between sensors to meters should <3m.
4. Advise use three core shielded wires as communication connection wires. Each core >0.5mm² connect A,B, Connect shielding layer to earth, and keep communication line away from strong electric cable or other strong electric field environment during wiring
5. The hall sensor opening locking screw must be tightened to ensure the closed-loop tightness of the sensor
RECOMMEND HALL SENSOR