DTSD1352/CT/C 3 Split Core Current Sensors With Modbus RTU RS485 Communication Din Rail Smart Meter
Application:PV Solar inverter,AC Energy Monitoring,Industry
Rated voltage(AC):3×220/380V, 3×380V, 3×57.7V/100V, 3×100V
Reference frequency:50Hz
Current Connect:Max 100A Connect/5A
Communication:RS485 Communication
- Overview
- Parameter
- Certificates
- Customer Questions & Answers
- Contact us
Overview
The DTSD1352-CT/C(ADL3000-E/CTC) kwh meter 3 phase dengan ct is an inverter-connectable smart meter designed for power supply systems, industrial and mining enterprises, and public utilities to calculate electricity consumption and manage electricity demand. It has the characteristics of high precision, small size and simple installation. Provide various data for the past 12 months, check the 31st harmonic content and total harmonic content, realize remote communication and remote control of switch input and relay output, and have the function of alarm output.
Equipped with RS485 communication port, suitable for MODBUS-RTU.DTSD1352-CT/C bi directional meter solar can be used in various control systems, SCADA systems and energy management systems. The instruments all meet the technical requirements for electric energy meters in the IEC62053-21 and IEC62053-22 standards.
Specification |
3 phase 3 wires, 3 phase 4 wires |
|
Voltage |
Reference voltage |
3×100V、3×380V、3×57.7/100V、3×220/380V |
Consumption |
<10VA(Single phase) |
|
Impedance |
>2MΩ |
|
Accuracy class |
Error±0.2% |
|
Current |
Input current |
3×1(6)A,3×1(6)A(Outlay transformer),3×10(80)A,3×10(100)A(Outlay transformer) |
Consumption |
<1VA(Single phase rated current) |
|
Accuracy class |
Error±0.2% |
|
Power |
Active, reactive, apparent power, error±0.5℅ |
|
Frequency |
45~65Hz,Error±0.2% |
|
Temperature |
-40℃~99℃ |
|
Energy |
Active energy(Accuracy class:0.5, 1), reactive energy(Accuracy class 2) |
|
Clock |
≤0.5s/d |
|
Energy pulse output |
1 active optocoupler output, 1 reactive optocoupler output |
|
Switching output |
1 Switching output |
|
Switching input |
1 optocoupler input |
|
Width of pulse |
80±20ms |
|
Pulse constant |
6400imp/kWh,400imp/kWh(Correspond with the basic current) |
|
Interface and communication |
RS485:Modbus RTU |
|
Range of communication address |
Modbus RTU:1~ 247; |
|
Baud rate |
1200bps~19200bps |
|
Relative temperature |
-25℃~+55℃ |
|
Relative humidity |
≤95℅(No condensation) |
DTSD1352/CTC 3 phase power meter data logger |
AC3*220/380V、3*380V、3*57.7/100V、3*100V 3*10 (100) A U、I、P、Q、S、PF、KWH、KVARH RS485 (MODBUS-RTU) LCD Display Frozen Data 2-31th Harmonic Measurement KWH Accuracy 0.5S,KVARH Accuracy 2 |
Parameters
Wiring:3P3W/3P4W Accuracy:Active Energy 0.5S,Negtive Energy 2 Voltage:3x57.7V/100V 3x380V 3x100V
Current:3x10(100)A Com Interface:2-Ways RS485 COM Interface (Optional),l Infrared COM InterfaceProtocol:Modbus DL/T645 Dimension:126.5*88*69.5mm |
![]() |
Dimension
Other Models
Shape | Model | Function | Optional function |
|
DTSD1352/C
|
Wiring:3P3W/3P4W Voltage:3x57.7V/100V 3x380V 3x100V Current:Under 80A direct connect, more than 80A via 5A ct connect Communication:RS485
|
1.RS485-MODBUS(C) 2.Multi-Tariff(F) 3.1DI1DO(K)orsecond road RS485 4.2-31 harmonic&THD(H) |
|
DTSD1352-CTC |
Wiring:3P3W/3P4W Voltage:3x57.7V/100V 3x380V 3x100V Current:with 3 pcs 100A cts Communication:RS485
|
3 and 4 cannot be selected together |
Specification | 3 phase 3 wires, 3 phase 4 wires | |
Voltage | Reference voltage | 3×100V、3×380V、3×57.7/100V、3×220/380V |
Consumption | <10VA(Single phase) | |
Impedance | >2MΩ | |
Accuracy class | Error±0.2% | |
Current | Input current | 3×1(6)A,3×1(6)A(Outlay transformer),3×10(80)A,3×10(100)A(Outlay transformer) |
Consumption | <1VA(Single phase rated current) | |
Accuracy class | Error±0.2% | |
Power | Active, reactive, apparent power, error±0.5℅ | |
Frequency | 45~65Hz,Error±0.2% | |
Temperature | -40℃~99℃ | |
Energy | Active energy(Accuracy class:0.5, 1), reactive energy(Accuracy class 2) | |
Clock | ≤0.5s/d | |
Energy pulse output | 1 active optocoupler output, 1 reactive optocoupler output | |
Switching output | 1 Switching output | |
Switching input | 1 optocoupler input | |
Width of pulse | 80±20ms | |
Pulse constant | 6400imp/kWh,400imp/kWh(Correspond with the basic current) | |
Interface and communication | RS485:Modbus RTU | |
Range of communication address | Modbus RTU:1~ 247; | |
Baud rate | 1200bps~19200bps | |
Relative temperature | -25℃~+55℃ | |
Relative humidity | ≤95℅(No condensation) |
Customer Questions & Answers
-
Answer:
In fact, you can contact us and we will confirm whether this product is suitable for you. This meter is three-phase, if you already have a single-phase inverter, you can also see if our ACR10R-D16TE is suitable for your needs.
Liana Song October 13, 2022 -
Answer:
They are one product, DTSD1352/C is our domestic model name in China, ADL3000-E/C is the model name facing the world, so they are all one product.
Liana Song October 13, 2022